Points on the drawing
Simulate it
Vibration reaching the servers
Everyday vibration (generators, traffic, works) reaches the racks through the floor and, over the years, wears the disks.
Vibration made audible.
Acceleration on this floor
– g
0 gGR-63-CORE Zone 4 test level: 1.65 g2 g
Tested with 1,700 kg of racks to GR-63-CORE Zone 4: in an earthquake they keep the racks anchored and connected.
The animation is illustrative and exaggerated.
See it working
A 900 mm high seismic plinth under a pair of operating server racks (1,500 kg), on a shake table to Telcordia GR-63-CORE Zone 4 (test report 213218, Virlab).
The table plays the Zone 4 synthetic earthquake along one axis for about 30 seconds. The plinth keeps both racks anchored and level while they run.
The table plays the Zone 4 synthetic earthquake along one axis for about 30 seconds. The plinth keeps both racks anchored and level while they run.
A slow sine sweep from 1 to 50 Hz and back finds the natural frequencies of the assembly, before and after the earthquake.
Container Pads under a container data centre with its racks, on a shake table to Telcordia GR-63-CORE Zone 4 (test report 203058).
The table plays the Zone 4 synthetic earthquake along one axis for about 30 seconds. The pads keep the container anchored and level.
The table plays the Zone 4 synthetic earthquake along one axis for about 30 seconds. The pads keep the container anchored and level.
The table plays the Zone 4 synthetic earthquake along one axis for about 30 seconds. The pads keep the container anchored and level.
A slow sine sweep from 1 to 50 Hz and back finds the natural frequencies of the assembly, before and after the earthquake.
A slow sine sweep from 1 to 50 Hz and back finds the natural frequencies of the assembly, before and after the earthquake.
A slow sine sweep from 1 to 50 Hz and back finds the natural frequencies of the assembly, before and after the earthquake.
Plays from YouTube in privacy-enhanced mode. Nothing loads from YouTube until you press play.
1Server racks
The problem
An earthquake does not need to knock a rack over to do damage. Peak accelerations above 0.5 g can break disks and make data unreadable, and racks that slide pull their cables out.
What we fit
An all-metal seismic plinth under each rack. Two linked frames absorb vertical and horizontal energy, the rack stays anchored and moves little sideways, so the cables stay connected. Qualified to Telcordia GR-63-CORE Zone 4. Where racks stand straight on the slab, the Non-Raised Floor Plinth takes up to 1,500 kg per rack at 4–5 Hz.
Typical choice
Non-Raised Floor Plinth, seismic plinth for racks100–1,500 kg · 4–5 Hz
Anti-vibration mounts for racks and data centres100–1,000 kg · 4.5 HzProven in seismic zones: EUIPO (2012), Telefónica (2013), metallic seismic plinths for the data centre.
The final choice depends on the load per mount, the speed and the environment. An engineer confirms it with you.
2Busbars, trays & ducts
The problem
Busbars, cable trays and ducts hang from the ceiling. When the building shakes they swing, and rigid hangers crack or tear the runs apart.
What we fit
Wire rope isolators: all-metal and multi-directional, they let the run move in all three axes and absorb the energy instead of breaking.
Typical choice
The final choice depends on the load per mount, the speed and the environment. An engineer confirms it with you.
3Rooftop chillers & HVAC
The problem
The roof is where a building sways the most. Chillers and air handlers on plain springs can bounce off their supports.
What we fit
Double springs with retention: low-frequency isolation in normal use, and a built-in restraint that holds the unit in place when the ground shakes.
Typical choice
The final choice depends on the load per mount, the speed and the environment. An engineer confirms it with you.
4Emergency generator
The problem
The generator has to start when the grid fails, often right after an earthquake. It needs isolation from its own vibration and has to stay where it is.
What we fit
All-metal mounts offered for seismic zones, or spring mounts with retention, so the generator is isolated in normal running and restrained in a quake.
Typical choice
The final choice depends on the load per mount, the speed and the environment. An engineer confirms it with you.
5Container data centres
The problem
Containerised data centres and equipment shelters stand outside on the ground and take the full ground motion.
What we fit
Container Pads: 6 to 14 double vertical suspensions with heavy-duty springs and stainless steel energy absorbers, anchored to the concrete and the container, for 16,000 to 30,000 kg per container.
Typical choice
Proven in seismic zones: Repsol (2014), plinths for the main data centre and container data centres.
The final choice depends on the load per mount, the speed and the environment. An engineer confirms it with you.
21 products

Anti-vibration metal cushion
- Load
- 0–3,000 kg
- Nat. freq.
- 10–35 Hz

Single anti-vibration springs
- Load
- 5–730 kg
- Nat. freq.
- 3–9 Hz

Wire rope isolators
- Load
- 5–1,000 kg
- Nat. freq.
- 7–15 Hz

Stainless axial vibration mounts
- Load
- 70–1,400 kg
- Nat. freq.
- 15–25 Hz

Square and oval base vibration mounts
- Load
- 42–5,000 kg
- Nat. freq.
- 15–20 Hz

Vibration mounts S402
- Load
- 30–700 kg
- Nat. freq.
- 15–20 Hz

Anti-vibration mounts for racks and data centres
- Load
- 100–1,000 kg
- Nat. freq.
- 4.5 Hz

Vibration mounts 954202-954203
- Load
- 50–7,000 kg
- Nat. freq.
- 11–22 Hz

FLEXAMOR vibration mounts
- Load
- on request
- Nat. freq.
- on request

Equal-frequency vibration mount
- Load
- 4–3,125 kg
- Nat. freq.
- 2–8 Hz

Double springs with retention
- Load
- 80–1,460 kg
- Nat. freq.
- 7–9 Hz

Conical shock mount 935009
- Load
- on request
- Nat. freq.
- 6–12 Hz

Vibration mounts 954412
- Load
- 1,000–3,000 kg
- Nat. freq.
- 15–20 Hz

Axial BF rubber vibration mounts
- Load
- 80–114 kg
- Nat. freq.
- 5 Hz

Anti-vibration floating slab
- Load
- on request
- Nat. freq.
- 1–4.5 Hz

Container Pad Seismic Vibration Isolator
- Load
- 100–10,000 kg
- Nat. freq.
- 3–9 Hz

Non-Raised Floor Plinth, seismic plinth for racks
- Load
- 100–1,500 kg
- Nat. freq.
- 4–5 Hz

Oval base metallic silentblock
- Load
- 20–50 kg
- Nat. freq.
- 40–60 Hz

VIBRALOCK washer
- Load
- on request
- Nat. freq.
- on request

Vibration mounts 954201
- Load
- 50–900 kg
- Nat. freq.
- 18–25 Hz

Vibration mounts 954416
- Load
- 350–3,000 kg
- Nat. freq.
- 15–25 Hz
By equipment
Pick the machine or equipment you want to isolate and see which mounts are used.
Where it has been installed · Seismic protection
4 projects in 4 countries
Seismic protection projects around the world. The orange points are the magnitude 5+ earthquakes of the last 7 days: click one to see what vibration it produces and how equipment is protected.
- projects
- 4
- countries
- 4
- M5+ earthquakes this week
- —
Case studies · Seismic protection

Energy · 2021
Krško, Slovenia
Twelve earthquakes on the shaking table, and not a single anomaly
Krško nuclear power plant
Read the case

Seismic protection · 2018
Europe
Server racks that ride out a Zone 4 earthquake
Schneider Electric · EUIPO data centre
Read the case

Seismic protection · 2013
Peru
110 racks from different makers on one seismic plinth system
Telefónica · main data centre
Read the case
Not sure which mount you need?
Our calculator tells you in 30 seconds.